APPLICATION
The intrinsically safe 6.3 GHz. pulse radar transmitter provides continuous level measurement up to 114.8’ (35m) with a 4-20 mA analog and HART digital signal output, and is configured via its integral push button display module or HART communicator. The non-contact liquid level sensor is intended for chemical and petroleum storage or process applications in above grade metal or reinforced concrete tanks or below grade tanks of any material. Select this sensor for harsh process conditions with corrosive or low dielectric media, heavy surface foam or agitation, higher pressure, steam, condensation or vapor, and installation in a flange fitting. Due to the wider beam angle, special attention should be given to ensure that the sensor is located with unobstructed measurement space. Typical applications include process tanks.
FEATURES
- 316L antenna with PTFE inner shield for corrosive media
- Configuration via push button display or HART communicator
- 6.3 GHz. pulse radar is unaffected by most foam and agitation
- 12” (30cm) dead band enables utilization of the entire tank
- LCD displays level in feet or meters with percent of span bar
- Optional display mode indicates the echo signal return curve
- Auto-temperature compensation for accurate measurement
- Fail-safe diagnostics with selectable signal fail-safe outputs
- Recognition, storage and rejection of false echo signal returns
- IP67 stainless enclosure with polycarbonate display window
PRICING
P/N | Description | From |
---|---|---|
LR26-5321-40-00 | 4″ ANSI flange, 316L w/PTFE shield | $2,900.00 |
LR26-5321-60-00 | 6″ ANSI flange, 316L w/PTFE shield | $3,000.00 |
LB12-1001 | Intrinsic safety barrier | $850.00 |
DOCUMENTATION
Data Sheet | Quick Start | Manual | 3D Model | Control Drawing | CSA Certificate | IECEx Certificate | ATEX Certificate | HART DD Files | Brochure
SPECIFICATIONS
Range: 12” to 114.8’ (30cm to 35m)
Frequency: 6.3 GHz.
Accuracy: ± 10mm
Dead band: 12” (30cm)
Beam angle: 20º
Configuration: Push button, HART 7
Memory: Non-volatile
Display type: LCD, dot matrix
Display units: Feet and meters
Display bar: Percent of span
Display graph: Echo signal curve
Supply voltage: 21.6 to 26.4 VDC
Max. consumption: 22.5 mA
Signal output: 4-20 mA, two-wire, HART 7
Signal invert: 4-20 mA, 20-4 mA
Signal fail-safe: 3.9 mA, 20.5 mA, 22 mA
Process temp.: F: -40º to 266º, C: -40º to 130º
Temp. comp.: Automatic
Storage temp.: F: -40º to 176º, C: -40º to 80º
Pressure: -14.5 to 580 psi (-1 to 40 bar)
Enclosure rating: IP67
Encl. material: 316L stainless steel w/silicone gasket
Encl. window mat.: Polycarbonate
Conduit entrance: (1) 1/2” NPT connector
Antenna material: 316L w/PTFE inner shield
Process mount: – 40: 4” flange (ANSI), – 60: 6” flange (ANSI)
Classification: Intrinsically safe
Approvals: ATEX IIG Ex ia II C T6…T3 Ga; IEC Exia IIC T6…T3 Ga; CSA Class I, Division 1, Groups A, B, C, D; Class II, Division 1, Groups E, F, G; (T6…T3) Class I Zone 0 AEx ia IIC (T6…T3) Ga Zone 20 AEx ia IIIC (T76ºC to T146ºC) Da Ex ia IIC (T6…T3) Ga Ex ia IIIC (T76ºC to T146ºC) Da
Entity parameters: Install per control drawing #301901
Certification: FCC
Compliance: CE, CRN, RoHS
PRODUCT SELECTION