APPLICATION

The general purpose optic leak switch provides liquid leak detection in and around secondary containment sumps, tanks and piping systems with a 1A relay output. Media examples include sulfuric acid and sodium hypochlorite. The submersible PP or PFA leak switch sensor is mounted through the containment wall or within the interstitial space, and connected to a PLC or relay controller.

FEATURES

  • Rugged polypropylene or PFA Teflon® sensor and cable for corrosive liquids
  • 60VA SPST relay selectable NO or NC via power supply wiring polarity
  • Sensor may be located up to 1000’ from a Flowline relay controller

PRICING

P/N Description From
LO10 LO10-1305 GP optic leak switch, PP, short, 1 relay, 3/4″ NPT $210.00
LO10-1325 GP optic leak switch, PP, short, 1 relay, 3/4″ G $230.00
LO10-1405 GP optic leak switch, PP, long, 1 relay, 3/4″ NPT $230.00
LO10-1425 GP optic leak switch, PP, long, 1 relay, 3/4″ G $250.00
LO10-2305 GP optic leak switch, PFA, short, 1 relay, 3/4″ NPT $375.00
LO10-2325 GP optic leak switch, PFA, short, 1 relay, 3/4″ G $415.00
LO10-2405 GP optic leak switch, PFA, long, 1 relay, 3/4″ NPT $415.00
LO10-2425 GP optic leak switch, PFA, long, 1 relay, 3/4″ G $460.00

COMPATIBLE ACCESSORIES

Indicators & Controllers
P/N Description From
LC40-1001 GP level switch controller LC40-1001 GP level switch controller, 120/240 VAC, 10A relay, PP $285.00
LM92 Single NEMA box LM92-1202 Single NEMA box, 35mm rail, windowed, PC $520.00
LM92 Double NEMA box LM92-2202 Double NEMA box, 35mm rail, windowed, PC $552.00
LC10 GP level switch controller LC10-1001 GP level switch controller, 120/240 VAC, 16A relay, PP $300.00
LC06 GP level switch junction box LC06-1001 GP level switch junction box, 6-pole terminal strip, PP $90.00
LC95-2001 Power supply LC95-2001 Power supply, 100-240 VAC, 24 VDC @ 0.45A $335.00

DOCUMENTATION

Orientation: Universal

Accuracy: ± 1mm in water

Repeatibility: ± 0.5mm in water

Supply voltage: 12-36 VDC

Consumption: 25 mA maximum

Contact type: (1) SPST relay

Contact rating: 60 VA, 1A maximum

Contact output: Selectable NO / NC

Process temp.: F: -40° to 176°, C: -40° to 80°

Pressure: 150 psi (10 bar) @ 25º C, derated @ 1.667 psi (0.113 bar) per ºC above 25º C

Sensor rating: -1XX5: NEMA 6 (IP68), -2XX5: NEMA 4X (IP65)

Sensor material: -1XX5: PP, -2XX5: PFA

Cable jack. mat.: -1XX5: PP, -2XX5: PFA

Cable type: 4-conductor, shielded, #22 AWG

Cable length: 10’ (3m)

Process mount: 3/4” NPT (3/4” G / Rp)

Mount. gasket: Viton® (G version only)

Classification: General purpose

Compliance: CE, RoHs

CONTROLLER

For pump, valve or alarm automation, package your leak detection switch with our remote level switch controller.

APPLICATION SUCCESS